1000kV特高压交流支柱瓷绝缘子的研制
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
根据晋东南—荆门1000kV特高压交流试验示范工程对支柱瓷绝缘子机械、电气、耐地震等性能的要求,首次采用污耐压法对支柱瓷绝缘子进行了污秽外绝缘设计、耐地震计算分析和性能评价。成功地研制了结构高度10m、额定弯曲破坏负荷16kN、扭转破坏负荷10kN.m、爬电距离30250mm的1000kV特高压交流工程用支柱瓷绝缘子。该绝缘子由5个单元件组成,具有优良的机械、污耐压和耐地震特性,可运行于c级污秽等级。试验验证和运行经验皆表明所研制的绝缘子的电气、机械特性等满足特高压交流试验示范工程的要求。
According to the requirements proposed by 1000 kV UHV AC demonstration project from southeastern Shanxi province to Jingmen in Hubei province,including the mechanical,electrical and seismic-resistant properties of post porcelain insulator,a pollution withstand voltage method was used to design the polluted external insulation of post porcelain insulator,and the calculation analysis of earthquake-resistant and the performance evaluation of anti-seismic were also carried out.Post porcelain insulator for 1000 kV UHV AC has been developed successfully by Fushun Electric Porcelain Manufacturing Co.,Ltd.,whose structural height is 10 m,rated bending failing load is 16 kN,torsion failing load is 10 kN·m,and creepage distance is 30250 mm.This insulator is composed of five single elements,and has excellent mechanical,pollution withstand voltage and earthquake-resistant properties,so it can be used in the area where pollution class is c.The simulations and service experience show that the mechanical and electrical properties of post porcelain insulator can satisfy the requirements proposed by 1000 kV UHV AC demonstration project from southeastern Shanxi province to Jingmen in Hubei province.
引文
[1]日本电气学会通信教育会.绝缘子[M].靳宝丰,译.北京:机械工业出版社,1987.
    [2]Witt H.Insulation levels and corona phenomena on HVDCtransmission lines[R].Gothenburg,Sweden:Chal mers Uni-versity,1961.
    [3]房柯夫,吴光亚,刘志强.1000kV交流变电站支柱和空心绝缘子污秽外绝缘设计的探讨[J].电瓷避雷器,2007(1):1-5.
    [4]吴光亚.1000kV级交流输变电工程外绝缘特性研究污秽绝缘部分总结国内外经验进行初步研究提出可供参考的外绝缘特性[R].武汉:武汉高压研究所,2005.
    [5]安德生J G.345kV及以上超高压输电线路设计参考手册[M].北京:电力工业出版社,1981.
    [6]丘志贤,白庆,李大楠,等.国产盘形和棒形支柱绝缘子耐污性能的试验研究[J].电瓷避雷器,1996(4):13-20.
    [7]吴光亚,徐涛,张锐,等.1000kV交流特高压试验示范工程支柱绝缘子和套管耐污性能研究[R].武汉:国网武汉高压研究院,2008.
    [8]Central ResearchInstitute of Electric Power Industry.Report on basic concept and external insulation design techniques of the polluted insulator in Japan[R].Tokyo,Japan:Central Re-search Institute of Electric Power Industry,2005.
    [9]Central Research Institute of Electric Power Industry.Central researchinstitute of electric power industry,report:182041[R].Tokyo,Japan:Central Research Institute of Electric Power In-dustry,1981.
    [10]Central Research Institute of Electric Power Industry.Centralresearch institute of electric power industry,report:181003[R].Tokyo,Japan:Central Research Institute of Electric Power Industry,1981.
    [11]吴光亚,张锐,徐涛,等.特高压线路沿线走廊污秽调查报告[R].武汉:国网武汉高压研究院,2006.
    [12]崔江流,张开贤.一九九零年华北大面积污闪事故调查报告[R].北京:国家电力公司发输电部,1990.
    [13]宿志一,刘湘生.二000年初辽宁、华北和河南电网大面积污闪事故调查报告[R].北京:国家电力公司发输电部,2001.
    [14]叶立茂、刘玉民.1000kV支柱绝缘子耐地震计算分析和耐地震性能评价[R].抚顺:抚顺电瓷有限公司,2007.
    [15]国网武汉高压研究院.国网武汉高压研究院试验报告:[2006]瓷字第194号[R].武汉:国网武汉高压研究院,2006.