基于结构-设备动力相互作用的户内式变电站抗震设计优化
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
结合黄屯110 kV变电站生产综合楼设计实例,在结构-电气设备复合体系中考虑二者相互动力作用,分析复合体系在大震弹塑性阶段的地震响应,并与不考虑相互作用的计算模型比较分析。分析结果表明,在大震作用下,电气设备参与整个复合体系的动力反应,使主结构的地震响应变大,同时电气设备本身的动力作用也变大,如仍采用传统的等效荷载法设计是偏不安全的,最后给出主结构和电气设备抗震设计的合理建议和优化措施。
A nonlinear dynamic response analysis with structure-equipments interaction of an integrative building in 110 kV Huangtun substation is studied.The results are compared with that of no structure-equipments interaction,which show it is necessary to considering structure-equipments interaction in integrative building of indoor substation.Under rare earthquake,the structure-equipments interaction should be considered,because the seismic responses of structure and equipments with consideration of the interaction are larger than those without consideration of the interaction.In this condition,the traditional equivalent load method will be insecure anymore.In the last,some optimization measures and reasonable suggestions about seismic design of structure and equipments are introduced.
引文
[1]李杰,陈淮,孙增寿,等.工业结构-设备体系在地震作用下的动力相互作用研究[J].地震工程与工程振动,1997,17(2):98-105.
    [2]李杰,陈淮,赵晓.结构-设备动力相互作用研究综述[J].世界地震工程,1994,5(2):5-12.
    [3]陈建兵,李杰.结构-设备体系动力相互作用研究[J].地震工程与工程振动,2001,21(3):70-74.
    [4]张向东.选煤厂结构-设备复合体系抗震研究[D].哈尔滨:中国地震局工程力学研究所,2004.
    [5]文波,牛荻涛,赵鹏.考虑结构-电气设备相互作用的配电楼系统地震反应分析[J].世界地震工程,2009,25(3):102-107.
    [6]文波.配电楼-电气设备系统的地震反应及减震控制研究[D].西安:西安建筑科技大学,2008.
    [7]朱炳寅.建筑结构设计问答及分析[M].北京:中国建筑工业出版社,2009.
    [8]GB50011—2010建筑抗震设计规范[S].
    [9]GB50260—96电力设施抗震设计规范[S].

版权所有:© 2023 中国地质图书馆 中国地质调查局地学文献中心