磁暴对中国电网的影响
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
通过比较2004年11月以来十几次磁暴数据与变压器中性点电流数据的相关性,证明了变压器发生的振动和噪声增大现象是磁暴在电网产生的地磁感应电流(GIC)所为,指出了磁暴对我国电网影响较大,磁暴对电网的影响已成为迫切需要研究的问题。
By comparison with relativity between the a dozen large number data of the magnetic storm since Nov.2004 and that of the current of the transformer neutra1 point,the paper proved that abnormal phenomenon of bigger vibration and greater noise in transformer arose from GIC in the electric power network,which induced by magnetic storm,and pointed out magnetic storm have greater impact on chinese power grid,and magnetic storms issue have an urgent need to study.
引文
[1]Albertson V D,Thorson J M,Miske S A,et al.The Effectsof Geomagnetic Storms on Electric Power System[J].IEEETransactions on Power Apparatus and System,1974,PAS-93(4):1 031-1 044.
    [2]Albertson V D,Thorson J M,Clayton R E John M T,et al.SolarInducedCurrentsinPowerSystem:CauseandEffects[J].IEEE Transactions on Power Apparatus and System,1973,PAS-92(2):471-477.
    [3]Kappenman J G,Albert V D,Bracing for the GeomagneticStorms[J].IEEE Spectrum Magazine,1990,27(3):27-33.
    [4]王梅义,吴竟昌,蒙定中.大电网系统技术[M].2版.中国电力出版社,1995.
    [5]马志强.变压器直流偏磁的原理性仿真[J].广东电力,2004,17(2):5-9.
    [6]Boteler D H.Geomagnetically Induced Currents:PresentKnowledge and Future Research[J].IEEE Trans on PowerDelivery,January 1994,9(1):50-58.
    [7]蒯狄正,刘成民,万达.直流偏磁对变压器影响研究[J].江苏电机工程,2004,23(3):1-5.
    [8]刘林玉,谢学武.500 kV主变压器异常声音分析[J].高电压技术,2005,31(4):85-87.
    [9]张建平,潘星.500 kV变压器异常噪声与振动的原因分析[J].浙江电力,2006,3:6-10.
    [10]盘学南,玉小玲.变压器运行噪声异常的探讨[J].变压器,2006,43(8):43-44.
    [11]李琪,高玉芬.2003年10—11月的大磁暴.地震地磁观测与研究,2006,27(2):43-47.
    [12]中国地震局地球物理研究所.磁暴报告[J].2003,25(4):4-8.

版权所有:© 2023 中国地质图书馆 中国地质调查局地学文献中心