钢筋混凝土异形柱框架-抗震墙结构振动台试验
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
通过12层1/7缩尺模型的模拟地震振动台试验,研究了钢筋混凝土异形柱框架-抗震墙结构体系的动力特性、地震反应及破坏形式.试验结果表明,该结构体系层间位移角能满足《规范》要求、抗震性能良好,适于在小高层住宅中采用.
The dynamic characteristics,response and failure form of reinforcement concrete frame-shearwall structure with specially shaped columns under different seismic intensities were studied by shaking table test of a 12-story model reduced scale in 1/7.The results showed that the structure system possesses good auti-seismic behavior and strong resistance against rarely happened earthquake,and this structure system can be suggested to use in mid-highrise residence building.