城市供水管网健康监测与诊断:Ⅲ.既有局部漏损识别方法之二
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
城市供水管网是城市最重要的生命线工程,相对于地上结构,地下供水管网具有更高的易损性。由于供水管网多埋于地下,管道的早期破坏难以及时发现。本文提出了既有供水管网局部漏损识别的第2个方法:假设在管网的不同位置存在不同程度的局部漏损,计算监测管段的流量,以监测管段流量的计算值和监测值之间的误差最小为目标来识别出局部漏损的位置和程度。通过算例分析对本文方法的有效性进行了验证,并与既有供水管网局部漏损识别的第1个方法进行了比较。结果表明,本文方法在准确率和分辨率两个方面均优于第1个方法。本文解决了供水管网健康监测和诊断中的一个基本问题。
Water distribution systems are the most critical lifeline facilities in cities,and are more fragile compared with above-ground structures.Losses are not easily discovered in water distribution systems at the early stage,since most water distribution systems are buried under ground.This paper proposes the second method for the identification of an existing local loss in a water distribution system,in which,the local loss is assumed at different positions with different extents,and the flow rates at monitoring stations are then calculated, and the loss is identified by minimizing the difference between calculated and monitored flow rates at monitoring stations.The effectiveness of the method is verified by an example.This method is compared with the first method,and it is shown that this method is better than the first method both in accuracy and resolution.This study resolves one fundamental problem in health monitoring and diagnosis of the water distribution systems.
引文
[1]梁建文.供水管网震害位置和震害程度的实时识别[J].地震工程与工程振动,2000,20(1):220-228.Liang J W.Real-time detection of position and degreeof seismic damage to water distribution systems[J].Earthquake Engineering and Engineering Vibration,2000,20(1):220-228.
    [2]梁建文,肖笛,赵新华,等.给水管网故障实时诊断方法[J].水利学报,2001,(12):60-67.Liang J W,Xiao D,Zhao X H,et al.Online fault di-agnosis of water distribution systems[J].Journal ofHydraulic Engineering,2001,(12):60-67.
    [3]梁建文,肖笛,张宏伟,等.给水管网故障实时诊断方法()[J].自然科学进展,2002,12(9):970-974.Liang J W,Xiao D,Zhang H W,et al.Online faultdiagnosis of water distribution systems()[J].Progress in Natural Sciences,2002,12(9):970-974.
    [4]Liang J W.Online location of seismic damage to a wa-ter distribution system[J].Earthquake Engineeringand Engineering Vibration,2003,2(2):181-187.
    [5]梁建文.城市供水管网健康监测与诊断:.既有局部漏损识别方法[J].地震工程与工程振动,2010(待刊).Liang J W.Health monitoring and diagnosis of a wa-ter distribution system:.Identification of an exis-tent local loss[J].Earthquake Engineering and Engi-neering Vibration,2010(in press).
    [6]高桑哲男.配水管网解析与设计[M].东京:森北出版株式会社,1978.150-153.Takakuwa T.Pipeline Network Analysis and Design[M].Tokyo:Morikita Publishing Company,1978.150-153.
    [7]Gupta R S.Hydrology and Hydraulic Systems[M].Englewood Cliffs:Prentice-Hall,1989.281-287.