某中学教学楼抗震鉴定及加固
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
上海市某中学教学楼建于1983年,原设计按6度抗震设防,存在明显不符合现行抗震规范的问题。为保证校舍继续安全使用,进行原始资料调查、现场检测及结构抗震性能评定,根据评定结果提出相应的加固方案。加固后的结构基本达到重点设防类抗震设防标准,结构整体性及承载力得到显著提高,从而改善了结构的安全状况。
A comprehensive seismic evaluation for a middle school teaching building in Shanghai was made.The building,completed in 1983,was designed with an earthquake fortification intensity of 6-degree,which cannot meet the demand for the current code.To insure the safety of the structure,initial data were investigated,on-site test was performed,and then seismic performance evaluation was made.According to the evaluation,it was put forward corresponding reinforcement measures,and the structure achieved the seismic fortification criteria.Which not only significantly enhanced the structural integrity and load-carrying capacity,but also improved the safety of the structure.
引文
[1]JGJ/T 136—2001贯入法检测砂浆抗压强度技术规程[S].
    [2]JGJ/T 23—2001回弹法检测混凝土抗压强度技术规程[S].
    [3]GB 50007—2002建筑地基基础设计规范[S].
    [4]JGJ 8—2007建筑变形测量规程[S].
    [5]GB 50023—2009建筑抗震鉴定标准[S].
    [6]GB 50009—2001建筑结构荷载规范[S].
    [7]GB 50003—2001砌体结构设计标准[S].
    [8]GB 50011—2001建筑抗震设计规范[S].
    [9]贾双寅,邱洪兴.结构可靠性鉴定与加固技术[M].北京:中国水利水电出版社,2002.
    [10]陈大川,李华辉.汶川地震后某中学综合楼抗震鉴定与加固设计[J].工业建筑,2009,39(8):4-7.