220kV断路器抗震性能地震模拟振动台试验
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
在汶川大地震中,变电站的大量电气设备受到了破坏。作为变电站的一种主要设备,断路器的抗震性能需要进行研究。根据地震中断路器的实际破坏情况,采用220kV单极瓷柱式断路器的足尺寸真型试件进行了地震模拟振动台试验研究。通过测定其在不同地面运动输入作用下设备关键部位的加速度、位移、应变等主要参数,研究了此断路器设备结构的动力特性、抗震性能以及支架的受力性能,并综合评定设备的抗震性能。试验结果表明:断路器的支柱瓷瓶根部处于复杂受力状态,是该设备抗震的薄弱环节;断路器的抗震设计要考虑下部支架对上部设备的动力放大效应。
Many substation equipments were damaged during Wenchuan earthquake.The seismic behavior of circuit breaker,main component of substation,should be studied.In this paper,shake table tests on a real full size circuit breaker are carried out to study the seismic behavior of the equipment.Seismic responses of accelerations,displacements and the strains of the key parts of the equipment are measured under different ground motions with different levels of peak ground accelerations.These parameters are used to analyze the dynamic characteristics,seismic performance of the equipment as well as the load-carrying capacity of the equipment bracket.The test results show that the bottom of the post insulator is seismic vulnerable part of the equipment due to its complex stress state.Dynamic amplification effects of the equipment bracket should be considered in seismic design of the equipment.
引文
[1]Xie Q,Zhu R Y.Damage to electric power grid infrastructure caused by natural disasters in China[J].IEEE Power and Energy Magazine,2011,9(2):28-36.
    [2]谢强.电力系统的地震灾害研究现状与应急响应[J].电力建设,2008,29(8):1-6.
    [3]杨亚弟,李桂荣.电气设施抗震研究概述[J].世界地震工程,1996,2:20-22,54.
    [4]董伟民,周书瑞.少油断路器及其减震体系的抗震研究[J].电力建设,1982,3(1):25-33.
    [5]吴惠中,周纪卿.KW4-500空气断路器地震响应分析[J].高压电器,1986,6:4-12.
    [6]杨亚弟,张其浩,苏文藻,等.多柱式电器设备抗震分析[J].地震学刊,1988,8:21-27.
    [7]李亚琦.电瓷型高压电气设备体系抗震性能分析[D].北京:中国地震局工程力学研究所,2002.
    [8]张军,陈大斌,张子引,等.220kV绝缘子及避雷器振动试验研究[J].电力技术经济,2009,21(4):47-50.
    [9]谢强,王亚非.软母线连接电气设备地震模拟振动台实验研究[J].中国电机工程学报,2011,31(4):112-118.
    [10]谢强,王亚非,魏思航.软母线连接的变电站开关设备地震破坏原因分析[J].电力建设,2009,30(4):10-14.
    [11]Hslkstcd R.Evaluation of the effect of mechanical operations on seismic qualification test of SF6circuit breakers[C]//Proceedings of the1991IEEE Power Engineering Society Transmission and Distribution Conference.Dallas,United States:IEEE,1991:473-477.
    [12]Girodet A.Seismic behavior of“CANDLE”type SF6outdoor circuit breakers and associated SF6insulated current transformers[J].IEEE Transactions on Power Delivery,1989,4(4):2100-2108.
    [13]GB50260—1996电力设施抗震设计规范[S].北京:中国计划出版社,1997.
    [14]IEEE Std-693-2005IEEE recommended practice for seismic design of substations[S].NJ:Piscataway,2006.