智能管理蓄电池放电特征
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
对北京市凤河营等地震台智能电源管理下的蓄电池放电数据进行处理和分析,发现蓄电池电压"平缓—快速—平缓"的下降过程可以表征蓄电池老化程度的现象,获得蓄电池小电流放电条件下每次放电过程的估算容量数据,实证蓄电池放电容量与温度之间存在正相关关系,且发现同批次蓄电池可能存在较大程度的容量差异。及时的数据处理分析,对于准确把握蓄电池工作状态、保障台站供电安全、合理安排蓄电池更新事务,可以起到积极的作用。
In this paper, the discharging data of battery that under intelligent management of Beijing Fengheying and other seismic stations was processed and analyzed. We found the battery voltage has a slow- fast- slow falling process and it can characterize the degree of battery aging. Under the conditions of low current, we estimated the battery capacity of each discharging process. Comparing discharge capacity with the temperature, we found they are positive related, and there is a great degree of capacity difference among the same batch of batteries. Timely processing and analyzing the data will do help to know the accurate working status of the battery, gurantee the security of electricity supply, and arrange for the battery update.
引文
陈立宝.对铅酸蓄电池放电时电压陡降复升的认识[J].蓄电池,2005,3:128-129.
    马士振,龚飞,张红旗,冯刚,等.智能电源管理系统在北京市测震台网的应用[J].地震地磁观测与研究,2012,33(5):292 -295.
    王晓峰,常征,张欢,等.地震台站管理服务器的设计[J].东北地震研究,2007,23(1):74-77.
    杨立杰,杨淑婷,等.蓄电池日常维护经验浅谈[J].中国科技纵横,2013,5:256-256.