摘要
本文研究频域介电响应规律,为频域介电法在油纸电容式高压套管绝缘状态中的应用提供依据。设计油纸电容式高压套管作为被试品,开展老化试验模拟套管服役状态。获得一系列不同老化周期的套管,测试其频域介电谱曲线。通过对被试套管的电容量(C)、介质损耗因数(tanδ)的频域谱曲线与老化时间以及聚合度的关系的研究,提出了一种油纸电容式高压套管绝缘状态评估的新方法,即基于频域介电谱分析油纸电容式高压套管绝缘状态评估方法。结果表明:(1)套管的电容量频域谱曲线在10-3~1Hz的频域段内能够明显反映其老化状态;(2)电容量的频域谱曲线的积分与老化时间(或聚合度倒数差)存在二次函数多项式关系;(3)在1Hz左右频率下的介质损耗因数能够更好的反映其老化状态。得出结论为频域介电响应法可应用与油纸高压套管绝缘检测与状态评估应用。
The paper is to study the applied regulation of frequency domain dielectric spectroscopy(FDS)in the insulation assessment of oil-paper condenser bushings.To achieve the result,a sample of oil-paper condenser bushings was designed and tested in aging.through the measurement of FDS of different aged samples and the study of relationship between aging and frequency domain curve of capacitance(C)and dielectric loss factor(tanδ),and the relationship between DP and frequency domain curve of C and tanδ,a new method of insulation assessment of oil-Paper condenser bushings was invented.The results:(1)the capacitance frequency domain dielectric characteristic quantity of the oil-paper insulation sample in 10~(-3)~1Hz can reflect the aging status of bushing;(2)There is a secondary polynomial function between aging time and frequency domain curve of capacitance(C)and between DP and frequency domain curve of C;(3)The dielectric loss factor reflects the aging status of bushing only in the 1Hz.Frequency domain dielectric response method can be applied to detection and condition assessment of the HV oil-paper bushings insulation.
引文
[1]司马文霞,兰海涛,杜林,等.套管末屏电压传感器响应特性研究[J].中国电机工程学报,2007,26(21):172-176.Sima Wenxia,Lan Haitao,Du Lin.Study on Response Characteristic of Voltage Sensor Mounted at the Tap of Transformer Bushing[J].PROCEEDINGS-CHINESE SOCIETY OFELECTRICAL ENGINEERING,2007,26(21):172-176.
    [2]Setayeshmehr A,Akbari A,Borsi H,et al.On-line monitoring and diagnoses of power transformer bushings[J].Dielectrics and Electrical Insulation,IEEE Transactions on,2006,13(3):608-615.
    [3]肖遥,夏谷林,程江平,等.一种容性电力设备的保护和监测新方案[J].南方电网技术,2012,4:002.Xiao Y,Xia G,Cheng J,et al.A New Protection and Monitoring Program for the Capacitive Power Apparatus[J].Nan fang Dian wang Ji shu,2012,6(4):1-5.
    [4]董淑建,何平.油纸电容式套管的发展与展望[J].电瓷避雷器,2006(5):5-7.DONG S,HE P.Development of Oil-impregnated Paper Condenser Bushing in History and in the Future[J][J].Insulators and Surge Arresters,2005,5:002.
    [5]陈伟根,赵立志,彭尚怡,等.激光拉曼光谱应用于变压器油中溶解气体分析[J].中国电机工程学报,2014,34(15):2485-2492.Chen Weigen,Zhao Lizhi,Peng Shangyi.Analysis of Dissolved Gas in Transformer Oil Based on Laser Raman Spectroscopy[J].PROCEEDINGS-CHINESE SOCIETY OFELECTRICAL ENGINEERING,2014,34(15):2485-2492..
    [6]Mac Alpine J M K,张潮海.糠醛浓度判断变压器绝缘纸寿命的综述[J].高电压技术,2001,27(4):63-64.Mac Alpine J M K.Study on the Paper Ageing in Transformer Oil Using Furfural Concentration[J].High Voltage Engineering,2001,4:025.
    [7]段宗超,吴广宁,高波.油纸绝缘频域介电谱特性与聚合度的关联影响规律研究[J].电网技术,2014,38(10):2881-2887.Duan zongchang,Wu Guangning,Gao Bo.Study of Linkage Effects Between Degree of Polymerization and Frequency Domain Dielectric Spectroscopy Characteristics of Oil-Paper Insulation[J].Power System Technology,2014,38(10):2881-2887.
    [8]廖瑞金,郝建,杨丽君,等.变压器油纸绝缘频域介电特征量与绝缘老化状态的关系[J].电工技术学报,2012,27(5):43-49.Lijun L R H J Y,Chao Y Q T.Relationship Between Frequency Domain Dielectric Characteristic Quantity and Aging Status of Transformer Oil-Paper Insulation[J].Transactions of China Electrotechnical Society,2012,5:005.
    [9]谢恒堃.电气绝缘结构设计原理:下册[M].机械工业出版社,1993.Xie H K.Electrical insulation design principles[M].China Machine Press,1993
    [10]卢理成,操敦奎,杨莉,等.绝缘纸聚合度测量方法及其劣化判据初探[J].华中电力,1990,5:003.Lu C L,Cao D K,Yang L,et al.Study on measurement methods of DP and deterioration criterion degree of polymerization of insulating paper[J].Central China Electric Power,1990,5:003
    [11]马元.变压器绝缘老化检测试验与寿命评估方法研究[D].山东大学,2010.Ma yuan.Studies on Methodology of Insulation Status Measurement and Life Assessment of Power Transformers[D].Shandong University,2010
    [12]Shroff D H,Stannett A W.A review of paper aging in power transformers[C]//IEEProceedings C(Generation,Transmission and Distribution).IET Digital Library,1985,132(6):312-319.
    [13]宋玉侠,罗传勇,阎雪梅,等.粘度法测定电工用纸/纸板聚合度的研究及应用[J].绝缘材料,2012(1):65-68.Yuxia S,Chuanyong L,Xuemei Y,et al.Measurement of Polymerization Degree of Paper/Paperboard by Viscometry for Electrical Engineering[J].Insulating Materials,2012,1:018.
    [14]李军,董立文,赵红.油浸式变压器的老化和寿命评估[J].高电压技术,2007,33(3):186-187.Li Jun,Dong Lihong,Zhao Hong.Aging and life assessment of oil-immersed transformers[J].High Voltage Engineering,2007,33(3):186-187.
    [15]廖瑞金,冯运,杨丽君,等.油纸绝缘老化特征产物生成速率研究[J].中国电机工程学报,2008,28(10):142-147.Liao R,Feng Y,Yang L,et al.Study on Generation Rate of Characteristic Products of Oil-paper Insulation Aging[J].PROCEEDINGS-CHINESE SOCIETY OFELECTRICAL ENGINEERING,2008,28(10):142.
    [16]Emsley A M,Stevens G C.Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformers[J].IEEProceedings-Science,Measurement and Technology,1994,141(5):324-334.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号

地址:北京市海淀区学院路29号 邮编:100083

电话:办公室:(+86 10)66554848;文献借阅、咨询服务、科技查新:66554700