72.5kV气体绝缘开关设备的抗震计算分析
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
建立了某型户内72.5 kV气体绝缘开关设备(gas insulated switchgear,GIS)的有限元模型,并根据GB/T 13540—2009采用响应频谱法对其进行了抗地震分析,给出了正常运行工况和地震载荷组合工况下的计算结果。结果表明:该电气设备满足烈度为9度的抗震性能要求,文中所确定的分析方法和步骤也适用于其他类型的高压设备的抗震分析。
A finite element model of some type of 72.5 kV gas insulated switchgear is built,and anti-seismic analysis for the model is conducted with the response spectrum method according to the national standard GB/T 13540—2009.Calculation results for the case of normal load and the case with both normal and earthquake loads show that this gas insulated switchgear meets the anti-seismic performance requirement for level 9 of earthquake intensity.The proposed analysis method and procedure can also be applied to anti-seismic performance of other high-voltage equipments.
引文
[1]GB/T13540—2009.高压开关设备和控制设备的抗震要求[S].GB/T 13540—2009.Seismic qualification for high-voltageswitchgear and controlgear[S].
    [2]IEC 62271-2—2003.High-voltage switchgear and control-gear-Part 2:Seismic qualification for rated voltages of72.5 kV and above[S].
    [3]曹枚根,周福霖,谭平.地震作用下断路器动力时程分析及阻尼效应研究[J].高压电器2010,46(7):27-35.CAO mei-gen,ZHOU Fu-lin,TAN Ping.Analysis on dy-namic time-history of circuit breaker and damping ratioeffect under earthquake[J].High Voltage Apparatus,2010,46(7):27-35.
    [4]刘新,张刚.组合电器耐地震计算分析[J].机械传动,2010,34(6):65-67.LIU Xin,ZHANG Gang.Anti-seismic analysis of the com-bined electric device[J].Journal of Mechanical Transmis-sion,2010,34(6):65-67.
    [5]柳永玉,王均梅,王晓琪.500kV电流互感器抗震性能分析[J].世界地震工程,2010,26(1):219-223.LIU Yong-yu,WANG Jun-mei,WANG Xiao-qi.Earth-quake resistant engineering[J].World Earthquake Engi-neering,2010,26(1):219-223.